ASSE (Plumbing) 1001-2008
- Performance Requirements for Atmospheric Type Vacuum Breakers
- standard by American Society of Sanitary Engineering, 02/18/2008
- Publisher: ASSE(Plumbing)
$23.00$45.00
The device shall: 1) Be installed downstream of the last control valve; 2) Not be subjected to backpressure; 3) Not be subjected to more than 12 hours of continuous water pressure; and 4) Be installed with its critical level (CL) not less than 6.0 inches (152.4 mm) above the flood level rim of the fixture or appliances served; or deck mounted/equipment mounted atmospheric vacuum breakers shall be installed in accordance with the manufacturer's instructions, with its critical level (CL) not less than 1.0 inch (25.4 mm) above the flood level rim of the fixture or appliance served.